Technical specification
410(L)*354(W)*536(H)mm
16.14(L)*13.94(W)*21.1(H)in
200(L)*297(W)*392(H)mm
7.87(L)*7.89(W)*15.43(H)in
35.5kg
Single-phase 200-240V 50/60Hz
1.32”OLED Screen
40L
140W(220V 50Hz)
45/60℃
-25℃~55℃
C1 Dry Cooler
Technical specification
580(L)*285(W)*531(H)mm
22.83(L)*111.22(W)*20.9(H)in
5-200W(220V 50Hz)
Single-phase 200-240V 50/60Hz
24kg
Automatically adjust the speed
according to the temperature
6kW@35°C
6kW@95°F
Accessories
Product specification
5m*2pcs
2pcs
1set
2pcs(Antminer)
1pcs
1pcs
6pcs
FAQ
Electrical questions
Would it be used when the voltage of C1 exceeds 240V?
The nominal voltage is 200-240V, but it can also be used within 250V.
What is the power consumption of the C1 system?
C1 tank is 100W, dry cooler is 180W.
Parameter questions
What is the protection temperature of the whole system?
Protection temperature is display 72 ℃. When the oil temperature exceeds 72°C, the system will automatically power off the mining machine and need to be restarted manually.
How noisy is the C1 Ultra?
Under normal circumstances, the tank noise is about 50dB, and the dry cooler noise is 65dB(A) 10m.
What is the material of C1 tank?
C1 liner material is stainless steel.
What is the C1 pipeline connector size?
The pipeline connection size of C1 is DN20 3/4" PT external thread.